The feasibility of ampacity control on HV transmission lines using the PLC system

dc.contributor.authorDe Villiers W.
dc.contributor.authorCloete J.H.
dc.contributor.authorHerman R.
dc.date.accessioned2011-05-15T15:53:39Z
dc.date.available2011-05-15T15:53:39Z
dc.date.issued2002
dc.description.abstractA frequency domain computer code, which predicts PLC (Power Line Carrier) signal attenuation, including the effect of coupling equipment, has been developed. The code was validated against measurements at ESKOM's Koeberg-Acacia 400 kV transmission line. Strong correlation, over a 28-day period, was observed between measured signal strength and predicted average phase conductor temperature. This significant finding might be exploited for real-time control of ampacity.
dc.description.versionConference Paper
dc.identifier.citationIEEE AFRICON Conference
dc.identifier.citation2
dc.identifier.urihttp://hdl.handle.net/10019.1/8725
dc.titleThe feasibility of ampacity control on HV transmission lines using the PLC system
dc.typeConference Paper
Files