The feasibility of ampacity control on HV transmission lines using the PLC system

Date
2002
Authors
De Villiers W.
Cloete J.H.
Herman R.
Journal Title
Journal ISSN
Volume Title
Publisher
Abstract
A frequency domain computer code, which predicts PLC (Power Line Carrier) signal attenuation, including the effect of coupling equipment, has been developed. The code was validated against measurements at ESKOM's Koeberg-Acacia 400 kV transmission line. Strong correlation, over a 28-day period, was observed between measured signal strength and predicted average phase conductor temperature. This significant finding might be exploited for real-time control of ampacity.
Description
Keywords
Citation
IEEE AFRICON Conference